The following describes various errors and troubleshooting steps.
This article is a work in progress.
General
Error message | What this means | Possible solution |
Device type unsupported |
The device is not supported. For example, you've scanned a Red5VAV controller using Proviso version 2.11 or earlier. |
|
Device type mismatch |
This error may occur if you are using the mass programming feature. For example, if you are programming multiple devices of the same type/model one after another but the device types do not match.
This error may also occur if you're attempting to recover the data. |
|
Data corrupted |
This error indicates the NFC memory is corrupted. |
|
Failed to transfer data to device |
Writing to the device was not successful. |
|
NFC
See below for best practices when using NFC:
- Double check the location of the NFC tag on the Delta Controls device and your smartphone reader. If you don't know where the NFC is located on your phone, you can look it up online.
Location of NFC tags on Delta Controls devices
- Make sure you place your phone directly above the NFC tag and do not move your phone until the successful message displays. Some users have better success when they rest their phones directly on the surface of the device.
- If you have a phone case, you may have more issues successfully connecting. Remove your phone case and try again.
- Make sure the values are written to the device as intended when using NFC to write values. It is recommended to wait approximately 10 seconds before peforming a second read with Proviso.