Viewing Metrics
The following objects are automatically created to provide access to metric data:
| Name | Instance | Description |
| Metrics - Occupant Temperature - mean | AV201 | Average occupant temperature during previous hour. |
| Metrics - Occupant Temperature - min | AV202 | Lowest occupant temperature during previous hour. |
| Metrics - Occupant Temperature - max | AV203 | Highest occupant temperature during previous hour. |
| Metrics - Occupant Humidity - mean | AV211 | Average occupant humidity during previous hour. |
| Metrics - Occupant Humidity - min | AV212 | Lowest occupant humidity during previous hour. |
| Metrics - Occupant Humidity - max | AV213 | Highest occupant humidity during previous hour |
| Metrics - Light Level - mean | AV221 | Average light level during previous hour. |
| Metrics - Light Level - min | AV222 | Lowest light level during previous hour. |
| Metrics - Light Level - max |
AV223 | Highest light level during previous hour. |
| Metrics - Sound Level - mean | AV231 | Average sound level during previous hour. |
| Metrics - Sound Level - min | AV232 | Lowest sound level during previous hour. |
| Metrics - Sound Level - max | AV233 | Highest sound level during previous hour. |
| Metrics - Occupancy Utilization | AV241 | Percentage of time the space was occupied during previous hour. |
Trending Metrics
You can set up Trend Log (TL) objects to monitor the metrics and collect sample data. This allows you to visualize the metrics on a line chart or in a table, or archive them if you'd like to report on them historically.
Forcing Updates
Metrics are normally computed at the beginning of every hour (12:00, 1:00, 2:00, etc.). However, you can force a metrics update at any time.
To force a metrics update:
- Create object BV292 with the name "Compute Metrics."
- Command the object to manual mode and set the object value to On.
Deleting Metrics
Metrics are archived for 30 days (available through MQTT). However, you can delete all metrics from the database at any time. Normally, this is done during commissioning to clear any metrics acquired during the installation and setup of the O3.
To delete all metrics:
- Create object BV291 with the name "Clear Metrics Database."
- Command the object to manual mode and set the object value to On.